AWG to mm² Converter (Wire Size)
Convert American Wire Gauge (AWG) to cross-sectional area in square millimeters (mm²) and conductor diameter.
Select Conductor Size
Physical & Electrical Specs1 AWG
Area in Circular Mils
83.69 kcmil
83,690 cmil75°C Conductor Ampacity
130 A
THWN / SE Copper ConductorCopper Resistance (20°C)
0.1239 Ω/kft
0.4066 Ω/kmAluminum Resistance (20°C)
0.203 Ω/kft
0.665 Ω/kmTypical Engineering Applications
Subpanel feeder lines (70A–125A), large central air conditioners, electric heat pumps, EV fast chargers (Level 2), and solar PV combiner feeds.
Metric Conductor Equivalent
Cross-Sectional Area (mm²)
42.4077mm²
Nominal gauge: 1 AWG
Solid Wire Diameter (Metric)
7.3481mm
Solid Wire Diameter (Imperial)
0.2893in
Step-by-Step Engineering Calculation
- 1Standard AWG Diameter formula:
- 2Diameter for : (0.2893 in)
- 3Cross-sectional Area:
Conversion Formula & Relationship
d_n = 0.127 × 92^((36-n)/39) mm | Area = (π / 4) × d_n²
Standard geometric progression defined in ASTM B258 for solid round electrical wire sizes.
Standard Conversion Example
Input: 12 AWG
Result: 3.31 mm² (2.05 mm diameter)
12 AWG corresponds to a solid conductor diameter of 2.053 mm and a cross-sectional area of 3.309 mm².
12 AWG = 3.31 mm² (2.05 mm diameter)
Quick Reference Conversion Table
| AWG | mm² | Common Application / Context |
|---|---|---|
| 4/0 (0000) | 107.22 mm² | Heavy service entrance |
| 2/0 (00) | 67.43 mm² | 200A residential service |
| 1/0 (0) | 53.49 mm² | 150A feeder |
| 2 AWG | 33.62 mm² | 100A subpanel feeder |
| 4 AWG | 21.15 mm² | 85A range / EV charger |
| 6 AWG | 13.30 mm² | 50A-60A circuits |
| 8 AWG | 8.37 mm² | 40A-50A circuits |
| 10 AWG | 5.26 mm² | 30A dryer / water heater |
| 12 AWG | 3.31 mm² | 20A standard outlets |
| 14 AWG | 2.08 mm² | 15A lighting circuits |
| 16 AWG | 1.31 mm² | Extension cords / fixtures |
| 18 AWG | 0.82 mm² | Thermostat / doorbell wire |
| 22 AWG | 0.33 mm² | Telecom / signal wiring |
| 24 AWG | 0.20 mm² | Ethernet Cat5e/Cat6 |
Frequently Asked Questions
Why does a smaller AWG number mean a thicker wire?
The AWG system originates from the number of drawing operations required to pull wire through progressive dies. Each drawing step reduced the wire diameter, so higher gauge numbers represent wire drawn through more dies.